![]() ![]() Ok so since found out it's a Menvier MF9200 Panel in situ (Forgot to mention that the call points are KAC 470 type) as the client wants the existing fire panel replaced does anyone know or had experience with Esp-fireline devices as in would they be compatible with a Haes Eclipse or C-Tec AFP type non-addressable control panel? or will i have to install one of those crappy looking ESP MAG2 MAGP2 panels? (but in all fairness i've not installed one of these ESP panels so they could be ok?) and are the existing batts that went in on the original install back in 1993!Īnyway my question is. I had a call-out this morning to look at a fire alarm system (not one of our contracted sites) and found a 1993 Menvier 2 zone non-addressable control panel (no model number? but the type where you have to turn the key left to silence and then turn the key right to reset if anyone knows the model?) anyway this is running Esp-Fireline (PSD-2) smoke detectors, apparently these had been "upgraded the last couple of years" needless to say the back-ups batts in the panel have never been replaced. ![]()